Mediflow — HVAC Quick Reference Calculator
HVAC Quick Reference · Field-Verified
W = 0.62198 × Pw / (P − Pw)
kPa — from psychrometric tables or wet-bulb reading
kPa — standard sea level = 101.325 kPa
Humidity Ratio W
kg/kg dry air
W (g/kg)
g/kg dry air
✓ Constant 0.62198 = ratio of molar masses: water (18.015) ÷ dry air (28.966). Field-verified standard.
φ = (Pw / Pws) × 100%
kPa
kPa — 20°C ≈ 2.339 · 25°C ≈ 3.169 · 30°C ≈ 4.246
Relative Humidity φ
%
h = 1.005T + W(2500 + 1.88T)
°C
kg/kg dry air
Enthalpy h
kJ/kg dry air
2500 kJ/kg = latent heat of vaporisation at 0°C · 1.005 = Cp of dry air · 1.88 = Cp of water vapour.
v = 0.287(T + 273.15)(1 + 1.607W)  ·  ρ = 1/v
°C
kg/kg dry air
Specific Volume v
m³/kg dry air
Air Density ρ
kg/m³
Qs (kW) = 1.23 × Q(L/s) × ΔT(°C) ÷ 1000
L/s
°C
Sensible Heat Qs
kW
Sensible Heat
Btu/hr
Airflow
CFM
Metric constant 1.23 W/(L/s·K) = ρ × Cp = 1.2 kg/m³ × 1.025 kJ/(kg·K) at standard conditions. Imperial equivalent: 1.08 Btu/hr per CFM·°F.
QL (kW) = 3010 × Q(m³/s) × ΔW(kg/kg)  ·  or 3.01 × Q(L/s) × ΔW
L/s
kg/kg — supply minus return
Latent Heat QL
kW
Latent Heat
Btu/hr
Airflow
CFM
QT = Qs + QL  ·  kW_refrig = QT  ·  SHF = Qs / QT
kW
kW
Total Heat QT
kW
Cooling Load
tons of refrigeration
SHF
sensible heat factor
Total Heat
Btu/hr
Enter sensible and latent heat values above.
V = Q/A  ·  Q = V·A  ·  A = Q/V
L/s
m² — round duct: π×(D/2)²
Velocity V
m/s
Velocity
FPM
Airflow
CFM
Typical duct velocities: main ducts 3–6 m/s · branches 2–4 m/s · grilles 1.5–2.5 m/s.
ACH = Q(m³/s) × 3600 / Volume(m³)
L/s
m³ — length × width × ceiling height
Air Changes per Hour
ACH
Airflow
CFM
Volume
ft³
Enter airflow and room volume.
hf = f × (L/D) × (V² / 2g)
Moody — smooth duct ≈ 0.01–0.02
m
m — round: actual dia; rect: 4A/P
m/s
Head Loss hf
Pa
Head Loss
in w.g.
Head Loss
mm w.g.
Re = V · D / ν
m/s
m
m²/s — air at 20°C ≈ 1.53×10⁻⁵
Reynolds Number Re
dimensionless
Enter velocity and duct dimensions.
RE = h₁ − h₄  ·  Wc = h₂ − h₁  ·  COP = RE / Wc
kJ/kg — superheated vapour at compressor inlet
kJ/kg — hot discharge gas
kJ/kg — subcooled liquid after condenser
Refrigeration Effect RE
kJ/kg
Compressor Work Wc
kJ/kg
COP
coefficient of performance
Condenser Duty h₂−h₄
kJ/kg
Enter enthalpy values from P-h chart.
ṁ = Qe / RE
kW
kJ/kg — from cycle calculation above
Mass Flow Rate ṁ
kg/s
Mass Flow Rate
kg/hr
ΔTlm = (ΔT₁ − ΔT₂) / ln(ΔT₁ / ΔT₂)
°C
°C
LMTD ΔTlm
°C
When ΔT₁ = ΔT₂ the logarithm is undefined — LMTD equals ΔT₁ in that case.
Q = U · A · ΔTm  ·  A = Q / (U · ΔTm)
kW
W/(m²·K) — air-water 20–100 · water-water 800–1500
°C — use LMTD from above
Required Area A
Required Area
ft²
P (kW) = Q(m³/s) × ΔP(Pa) / (1000 × η)
L/s
Pa — 1 in w.g. ≈ 249 Pa
0.0–1.0 — centrifugal: 0.65–0.80
Fan Brake Power
kW
Fan Brake Power
HP
Air Power (ideal)
kW
Airflow
CFM
Air Power (ideal) = Q × ΔP / 1000 with no efficiency loss. Brake power = Air Power ÷ η.
Q₂ = Q₁(N₂/N₁)  ·  ΔP₂ = ΔP₁(N₂/N₁)²  ·  P₂ = P₁(N₂/N₁)³
RPM
RPM
L/s
Pa
kW
New Airflow Q₂
L/s
New Pressure ΔP₂
Pa
New Power P₂
kW
Power Saving
% reduction
Enter speed and original performance values.
P = V · I · cosφ  ·  Q = V · I · sinφ  ·  I = P / (V · cosφ)
V — AU single phase = 230 V · US = 120 V / 240 V
A
0.0–1.0 — HVAC motors typically 0.80–0.90
Real Power P
W
Apparent Power S
VA
Reactive Power Q
VAR
P = √3 · V · I · cosφ  ·  I = P / (√3 · V · cosφ)
V — AU three phase = 415 V · US = 208 V / 480 V
W
0.0–1.0
Line Current I
A per phase
Apparent Power S
kVA
Reactive Power Q
kVAR
C_indoor = C_outdoor + G / Q
ppm — global ambient ≈ 422 ppm (2024)
m³/s — sedentary adult ≈ 0.004–0.006 m³/s per person
m³/s — outdoor air supply rate
Steady-State CO₂
ppm
Rise Above Outdoor
ppm rise
Enter CO₂ generation and ventilation rate.
ASHRAE 62.1 target: below 1000 ppm indoor. WELL standard: below 900 ppm. Values above 1100 ppm indicate inadequate outdoor air supply.
Based on field-verified HVAC formulas. Metric constants: sensible heat 1.23 W/(L/s·K); humidity ratio 0.62198; ρ·Cp ≈ 1.206 kJ/(m³·K). Imperial: 1.08 Btu/hr·CFM·°F. Always confirm unit consistency before applying results to design. Refer to AS 1668, ASHRAE Handbooks, and a licensed mechanical engineer for detailed engineering design. Prepared by Mediflow.